CN-AIOI Address & Control Unit

Original manufacturer
Consilium / Salwico
Name
CN-AIOI Address & Control Unit
Model
CN-AIOI
Part number
023261

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsEN54-17:2005/AC:2007; EN54-18:2005/AC:2007; IACS E10. Printed 2531-CPR-232.1707 / DoP CN-1707; current validity unknown.
Manufacturer Article Number023261
Compatible Control SystemsNSAC-1; TERRA FIRE; TERRA ONE.
Loop Voltage34 VDC nominal; 20–38 VDC working.
Loop Current0.3 mA working; 10 mA alarm.
External Power24 VDC ±20%; 50 mA input (about 15 mA per relay). Separate supply required when relays are used.
Detector / Switch SupplyIN1/IN2: 12–15 V DC supplied from the loop.
Inputs / Relay Outputs2 inputs; 3 programmable relay outputs. Two relay outputs can supervise an external control cable.
Relay Contact LoadMaximum 24–48 VDC / 1.0 A.
Address / Function Switches8-way address DIP; 6-way function DIP.
Enclosure / EnvironmentIP65; PC/ABS; −10 to +55 °C; 0–95% RH.
Weight500 g ±5%.
Printed Standards / Safety ScopeEN54-17:2005/AC:2007; EN54-18:2005/AC:2007; IACS E10. Printed 2531-CPR-232.1707 / DoP CN-1707; current validity unknown.
Fire Mode / Device SelectionDIP 6 ON. DIP 1–3: 0 Detector, 1 Smoke, 2 Heat, 3 Manual call point, 4 IS, 5 Fire, 6 Sprinkler, 7 Flame. Normally use NS-AIN1 for intrinsically safe devices.
Fire-mode Power SupervisionExternal 24 V supply is NOT supervised in fire mode.
Conventional Detector InterfaceRemote LED indication. If the detector lacks internal Ri, add about 330 Ω in series to distinguish fire from short-circuit fault.
External Fire InterfaceIN1 fire closing contact; IN2 pre-alarm closed contact / external fault open circuit. OUT1 reset pulse about 3 s; OUT2/3 programmable.
Terra One LimitationPre-alarm is unavailable in the Terra One single-loop panel.
Sprinkler InterfaceFlow alarm delayed about 15 s to reject pressure shocks; IN2 section valve supervised for fully open position.
I/o ModeDIP 6 OFF. 2 digital inputs; 2 external cable supervisions; 3 relay outputs; external 24 V supervision.
I/o External Supply / SuppressionExternal 24 V is needed for relay activation and IN3/4 supervision. Fit a switch-off diode to external relays/contactors to prevent voltage spikes.
Safe / Unsafe InputsSafe: IN1 confirms safe position; Unsafe: IN2 confirms unsafe position.
Failsafe / WatchdogFailsafe opens relays on power loss. Watchdog requires RKS06 and holds relay position for a period after loop power loss.
Auto FunctionOpens relays for fire, fault, or disabled-then-fire devices within ±3 addresses.
Mode 11 Special ActionThe starred exception automatically CLOSES relays if any disabled device on the same loop enters fire alarm.
I/o Mode Matrix: 0–50 General I/O; 1 bell control (RKS05 only); 2 Safe; 3 Safe+Failsafe; 4 Failsafe+Auto; 5 Safe+Failsafe+Auto.
I/o Mode Matrix: 6–96 Safe+Failsafe+Watchdog+Auto; 7 Failsafe+Watchdog+Auto; 8 Safe+Unsafe; 9 Safe+Unsafe+Failsafe.
I/o Mode Matrix: 10–1610 Failsafe+Watchdog; 11 Failsafe+Watchdog+Auto*; 12 Failsafe; 16 Local timer. Modes 6,7,10,11 require RKS06.
Dsci Wiring RecommendationInterconnect/crossconnect the positive leads to one terminal using a jumper or similar.
Original Installation DrawingsAll 8 original pages retained: terminal numbers, enclosure/mounting dimensions, DIP diagrams and connection examples. Refer to original PDF before installation.

Compatibility

  • NSAC-1
  • TERRA FIRE
  • TERRA ONE

Accessories

  • RKS06 watchdog/power-loss relay delay; RKS05 required for mode1 bell control.
  • NS-AIN1 recommended for normal intrinsically safe device applications.