Charger M H Power Supply and Battery Charger

Original manufacturer
Consilium / Salwico
Name
Charger M H Power Supply and Battery Charger
Model
Charger M H
Part number
5100062-01A

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsNot provided by manufacturer
Manufacturer Article Number5100062-01A
Psu Input28 VDC
Operating Voltage Range19-30 VDC
Current Consumption (at 24 V, Battery Supply Only)43 mA
Max. Output Current8 A
Cable Terminals2.5 mm²
Ntc Resistor10 kΩ 2%, B=3977, 3×3
Ga Input Resistor10 kΩ
Operating Temperature Range-40 °C to +85 °C (Tx)
Weight (with Housing)140 g ± 5%
Spare Part No.5100061-03A
Manufacturer-listed SystemTS1000 (2022 V T document)
Address ConfigurationSW1 poles 1-7 set binary physical address; it must match system configuration
Backbone Power ChannelsSW1 pole 8: channel 1; pole 9: channel 2. ON deactivates, OFF activates
Power Output / Sw1 Pole 10ON: always active; set output to "not used" in configuration to avoid faults. OFF: programmable
One / Two-module SetupSingle: 8+9 OFF. Dual: module 1 8 OFF/9 ON; module 2 8 ON/9 OFF
Redundant Earth SupervisionFor the two-module redundant method, disable earth supervision on ONE Charger M by removing its PCB jumper
Battery Capacity / Sw2Poles 1/2 ON/ON: 0-12 Ah; OFF/ON: 12-24 Ah
Forbidden Sw2 SettingsON/OFF and OFF/OFF not allowed. Wrong charging setting can overcharge, undercharge or overload PSU
Battery TypeValve-regulated lead-acid (AGM) batteries only
Ntc Sensor LocationExternal NTC on battery holder or as close as possible; NOT directly on battery
Charging Temperature ConditionExternal NTC adjusts charging; optimum battery performance specified between -5 °C and +40 °C
Deep-discharge HandlingNot designed to recover deeply discharged batteries; replace or use a separate charger designed for that purpose
Low-battery Output CutoffWith charging enabled and PSU1/2 power absent: below 21 VDC ±0.5 V shuts outputs off
Standby / Battery SafetyStandby still draws approx.25 mA. After >1 hour, physically disconnect battery to prevent further deep discharge
General Alarm (morse) Scope24 VDC GA input via hardware to internal BBI; cabinet-common BBI only, not between stretched bus sections
Output Capacity ConditionMaximum power output depends on PSU capacity and Backbone Bus load
Ntc / Ga IndicatorsNTC: green=overheat, yellow=cable break, off=OK. GA: green=general alarm active, off=OK
Communication / Safe-state LedsCOM green flashing: communication OK but unconfigured. PS yellow flashing + COM off: module not functional
Wiring ReferenceRetain original p2 diagram for PSU1/2, mains/emergency monitors, power output, GA, battery and NTC terminals
MountingMount on a horizontal 35 mm DIN rail
Dimensions99 mm high ×114 mm deep ×29 mm wide; original drawing also marks 23 mm subdimension