TERRA ONE Fire Alarm Panel
- Original manufacturer
- Consilium / Salwico
- Name
- TERRA ONE Fire Alarm Panel
- Model
- TERRA ONE
- Part number
- 5100429-00B
Supply availability and delivery time require confirmation. A catalog reference does not imply stock.
Specifications
| Manufacturer approvals / certifications | Not provided by manufacturer |
|---|---|
| Manufacturer Article Number | 5100429-00B |
| Manufacturer-listed Line Devices | CN-AIOI, CN-BI, CN-DPH, CN-H/A1R, CN-H/CS, CN-HIOP-BCN SCI, CN-HIOP-SB SCI, CN-HIOP-SDR SCI, CN-MCP2-DSCI, CN-MCP2-SCI, CN-MCP2-SCI-WP, CN-P, CN-PH, CN-PS, CN-PS-DSCI, CN-PYH, CN-SB-DSCI |
| En54-2 Functions In Historical Document | 7.8 alarm devices; 7.9.1 alarm routing; 7.11 output delays; 7.12.3 Type C dependency; 7.13 alarm counter; 8.3 point faults; 8.9 fault routing; 9.5 disablement; 10 test |
| Battery Space / Runtime Condition | Max dimensions 152(L) ×99(W) ×99(H) as manufacturer printed. Specified maximum 36 h normal operation then 30 min fire alarm with indications and bells active |
| Mounting Drawings | Use original p3 exterior and p4 rear/recessed mounting drawings, cable knockouts and fixing pattern; do not infer dimensions from the photograph |
| Relay Outputs | 4 single-pole normally open closing contacts: 24 VDC/2 A or 48 VDC/1 A; alarm/fault routing, fail-safe fire doors or ventilation |
| Ethernet / Network Restriction | Standard Ethernet for web access, support and remote diagnostics; stand-alone fire alarm panel CANNOT be networked |
| Document Storage | Drawings, manuals, protocols and other required panel documentation must be stored in a separate cabinet |
| Panel Access / Cable Glands | Lock/fire-brigade key for keyboard. Cable access from top or upper rear only; cable glands NOT included |
| Historical Standard References | Manufacturer lists EN54-2, EN54-4, EN54-13 and SS3654; this is not a claim of current certification |
| Alarm-delay Input Safety | One closing-contact on/off input; cable NOT supervised for short circuit or cable break |
| Bell / Flashlight Outputs | 3 ×24 VDC /700 mA; polarity switches when active; short-circuit and break detection |
| Recessed Mounting Cutout | 315 ±2 mm width ×332 ±2 mm height, per original p4 cutout drawing |
| Normal Current Consumption | 100 mA (28 VDC) |
| Ingress Protection | IP30 |
| Cable Terminals | 2.5 mm² |
| Manufacturer-listed System | TERRA ONE (2021 J document) |
| Configuration / Addressing | Basic setup at panel; texts via panel or PC Ethernet. Integrated address programmer accessed by service engineer after removing front; select device address in panel UI |
| User / Service Functions | Disable zones, outputs or individual devices; alarm-delay on/off at panel/external input; one-person device test, test list and contaminated-detector service list |
| Terminal Wiring Reference | Retain original p3 terminal table for 24 VDC, input, bells, four relays, Ethernet, RS485 and loop OUT/A and IN/B. Ethernet does not permit panel networking |
| Power Output / Revision Limit | 1 ×24 VDC /180 mA for Rev. A06 and later; Rev. A05 and earlier 130 mA. For alarm transmitter/door magnets; short-circuit supervision |
| Configuration Backup | Zone allocation/simple Cause & Effect at panel; customer text by panel or PC Ethernet; PC supports backup and restoration |
| Panel Function | Compact stand-alone fire alarm panel with one analogue addressable sensor loop for smaller installations |
| Loop Cable / Load Limits | Max 1000 m total loop-out to loop-in; per km max 50 Ω and 100 nF. Max 150 addresses across max 24 zones |
| Battery Selection / Supply | 12 Ah; 2 ×12 V sealed lead-acid. Batteries NOT included; recommended Fiamm FG21202 or Yuasa NP 12-12 |
| Device Programming Restriction | Built-in device programming base for replacement; soft customer codes NOT supported, use open code |
| Required Reference Manuals | User Guide 5100502; Installation, Service and Maintenance 5100503; Quick Guide 5100504 |
| Colour | Front: Light gray (RAL7035) Backbox: Dark gray (Pantone Cool Gray 9) |
| Operating Temperature Range | -5°C to +40°C |
| Enclosure, Material | Plastic (ABS/PC) |
| Weight | 1,6 kg (without batteries) |
| Mains Supply | 100-240 VAC, 50/60 Hz |
Compatibility
- Requires technical confirmation; manufacturer compatibility evidence is not provided.
Accessories
- Not provided by manufacturer
Original documents & sources
Source pages
- https://www.consiliumsafety.com/content/uploads/products/en/5100429-00/5100429-00B_TERRA%20ONE_I0_EN_2021_J.pdf
- https://www.consiliumsafety.com/content/uploads/products/en/5100429-00/5100429-00B_TERRA%20ONE_I0_EN_2021_J.pdf
- https://www.consiliumsafety.com/content/uploads/products/en/5100429-00/5100429-00B_TERRA%20ONE_I0_EN_2021_J.pdf
Original manufacturer data retained. Product enquiry and technical sourcing by MAXONE Marine. Last reviewed: Not provided.