Connecting Global Safety Technology

TERRA ONE Fire Alarm Panel

Original manufacturer
Consilium / Salwico
Name
TERRA ONE Fire Alarm Panel
Model
TERRA ONE
Part number
5100429-00B

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsNot provided by manufacturer
Manufacturer Article Number5100429-00B
Manufacturer-listed Line DevicesCN-AIOI, CN-BI, CN-DPH, CN-H/A1R, CN-H/CS, CN-HIOP-BCN SCI, CN-HIOP-SB SCI, CN-HIOP-SDR SCI, CN-MCP2-DSCI, CN-MCP2-SCI, CN-MCP2-SCI-WP, CN-P, CN-PH, CN-PS, CN-PS-DSCI, CN-PYH, CN-SB-DSCI
En54-2 Functions In Historical Document7.8 alarm devices; 7.9.1 alarm routing; 7.11 output delays; 7.12.3 Type C dependency; 7.13 alarm counter; 8.3 point faults; 8.9 fault routing; 9.5 disablement; 10 test
Battery Space / Runtime ConditionMax dimensions 152(L) ×99(W) ×99(H) as manufacturer printed. Specified maximum 36 h normal operation then 30 min fire alarm with indications and bells active
Mounting DrawingsUse original p3 exterior and p4 rear/recessed mounting drawings, cable knockouts and fixing pattern; do not infer dimensions from the photograph
Relay Outputs4 single-pole normally open closing contacts: 24 VDC/2 A or 48 VDC/1 A; alarm/fault routing, fail-safe fire doors or ventilation
Ethernet / Network RestrictionStandard Ethernet for web access, support and remote diagnostics; stand-alone fire alarm panel CANNOT be networked
Document StorageDrawings, manuals, protocols and other required panel documentation must be stored in a separate cabinet
Panel Access / Cable GlandsLock/fire-brigade key for keyboard. Cable access from top or upper rear only; cable glands NOT included
Historical Standard ReferencesManufacturer lists EN54-2, EN54-4, EN54-13 and SS3654; this is not a claim of current certification
Alarm-delay Input SafetyOne closing-contact on/off input; cable NOT supervised for short circuit or cable break
Bell / Flashlight Outputs3 ×24 VDC /700 mA; polarity switches when active; short-circuit and break detection
Recessed Mounting Cutout315 ±2 mm width ×332 ±2 mm height, per original p4 cutout drawing
Normal Current Consumption100 mA (28 VDC)
Ingress ProtectionIP30
Cable Terminals2.5 mm²
Manufacturer-listed SystemTERRA ONE (2021 J document)
Configuration / AddressingBasic setup at panel; texts via panel or PC Ethernet. Integrated address programmer accessed by service engineer after removing front; select device address in panel UI
User / Service FunctionsDisable zones, outputs or individual devices; alarm-delay on/off at panel/external input; one-person device test, test list and contaminated-detector service list
Terminal Wiring ReferenceRetain original p3 terminal table for 24 VDC, input, bells, four relays, Ethernet, RS485 and loop OUT/A and IN/B. Ethernet does not permit panel networking
Power Output / Revision Limit1 ×24 VDC /180 mA for Rev. A06 and later; Rev. A05 and earlier 130 mA. For alarm transmitter/door magnets; short-circuit supervision
Configuration BackupZone allocation/simple Cause & Effect at panel; customer text by panel or PC Ethernet; PC supports backup and restoration
Panel FunctionCompact stand-alone fire alarm panel with one analogue addressable sensor loop for smaller installations
Loop Cable / Load LimitsMax 1000 m total loop-out to loop-in; per km max 50 Ω and 100 nF. Max 150 addresses across max 24 zones
Battery Selection / Supply12 Ah; 2 ×12 V sealed lead-acid. Batteries NOT included; recommended Fiamm FG21202 or Yuasa NP 12-12
Device Programming RestrictionBuilt-in device programming base for replacement; soft customer codes NOT supported, use open code
Required Reference ManualsUser Guide 5100502; Installation, Service and Maintenance 5100503; Quick Guide 5100504
ColourFront: Light gray (RAL7035) Backbox: Dark gray (Pantone Cool Gray 9)
Operating Temperature Range-5°C to +40°C
Enclosure, MaterialPlastic (ABS/PC)
Weight1,6 kg (without batteries)
Mains Supply100-240 VAC, 50/60 Hz

Compatibility

  • Requires technical confirmation; manufacturer compatibility evidence is not provided.

Accessories

  • Not provided by manufacturer

Original documents & sources

Source pages