Connecting Global Safety Technology

IC44 SS WP Stainless-Steel Weatherproof I/O Interface Module

Original manufacturer
Consilium / Salwico
Name
IC44 SS WP Stainless-Steel Weatherproof I/O Interface Module
Model
IC44 SS WP
Part number
5100782-00A

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsNot provided by manufacturer
Ingress ProtectionIP66
Relative Humidity≤ 95 % RH non-condensing
Ambient Temperature-40°C to +70°C
Cable GlandM20 for cable ø 6–13mm
Cable Gland MaterialNickel plated brass
Cable Terminals2.5 mm2
Enclosure MaterialStainless steel AISI 304
Gasket MaterialPolyurethane and silicone
ColourPolished surface
Weight≈1 kg
CertificationEN 50155
External 24 Vdc Nominal Voltage24 VDC
External 24 Vdc Working Voltage19 - 30 VDC
External 24 Vdc Max Current100 mA
External 24 Vdc Nominal Power Output24 VDC, 80 mA
External 24 Vdc Max Input Load15 mA per input. Pulsed.
External 24 Vdc Input Pulse Length100 ms
Loop-powered Nominal VoltageNot provided by manufacturer
Loop-powered Working VoltageNot provided by manufacturer
Loop-powered Max CurrentNot provided by manufacturer
Loop-powered Nominal Power OutputNot provided by manufacturer
Loop-powered Max Input Load5 mA per input. Pulsed.
Loop-powered Input Pulse Length8 ms
Inputs4 inputs for closing contacts or NPN/PNP proximity switches
Relay Output Rating4 pcs 2-pole relay contacts, max 30 VDC, 1A
Power Output24 VDC, 80 mA
Loop Nominal Voltage35 VDC
Loop Working Voltage22 - 38 VDC
Loop Current Consumption0.3 mA
Input End Of Line Resistor30kΩ (Included)
Sw2 Dip 8 RequirementSW2 DIP 8 must always be ON.
Address SwitchSW1 sets the loop address.
External 24 Vdc Input Terminals13-16, 18-36 VDC, optional
Isolated 24 Vdc Output Terminals21-22, max 5 mA for local indicators; active only with external 24 VDC input on 13-16
Output Terminals23-46, NC/NO output 1 to 4
External Earth ConditionConnect the enclosure external earth connection to earth; see the Installation & Commissioning manual.
Source DatasheetData sheet no. 5100782-00A_IC44 SS WP_T_EN_2019_B
Specification Change NoticeThe specifications described herein are subject to change without notice.
Proximity Switch Supply ConditionNOTE! The use of proximity switches requires external 24 VDC supply.
Body Width150 mm
Body Height150 mm
Body Depth80 mm
Overall Width200 mm
Overall Height196 mm
Mount Width175 mm
Mount Height106 mm
Wall Mounting Holes4 holes; max screw thread M8
External Earth Connection ThreadM6
Installation CautionCAUTION! Do not use electrical screwdriver. Maximum torque 2 Nm.
Table 1. Id For Different Operation Modes Set By Sw2 Dip 1 To 5 (operation-modes) — Row 1 — Mode1
Table 1. Id For Different Operation Modes Set By Sw2 Dip 1 To 5 (operation-modes) — Row 1 — Function2 inputs and 2 outputs
Table 1. Id For Different Operation Modes Set By Sw2 Dip 1 To 5 (operation-modes) — Row 1 — ExampleEmulates control unit CM-2x
Table 1. Id For Different Operation Modes Set By Sw2 Dip 1 To 5 (operation-modes) — Row 2 — Mode2
Table 1. Id For Different Operation Modes Set By Sw2 Dip 1 To 5 (operation-modes) — Row 2 — Function4 inputs and 4 outputs
Table 1. Id For Different Operation Modes Set By Sw2 Dip 1 To 5 (operation-modes) — Row 2 — ExampleEmulates control unit CM-4x
Sw2 Function Settings (sw2-function-settings) — Row 1 — Sw2 Dip6
Sw2 Function Settings (sw2-function-settings) — Row 1 — SettingON
Sw2 Function Settings (sw2-function-settings) — Row 1 — FunctionMust be set when external 24VDC power supply is used.
Sw2 Function Settings (sw2-function-settings) — Row 2 — Sw2 Dip7
Sw2 Function Settings (sw2-function-settings) — Row 2 — FunctionNot used
Terminal Connections (terminal-connections) — Row 1 — Terminal Range1-12 and 47-50
Terminal Connections (terminal-connections) — Row 1 — SignalIN+
Terminal Connections (terminal-connections) — Row 1 — ConnectionInput 1 to 4
Terminal Connections (terminal-connections) — Row 2 — Terminal Range1-12 and 47-50
Terminal Connections (terminal-connections) — Row 2 — SignalIN-
Terminal Connections (terminal-connections) — Row 2 — ConnectionInput 1 to 4
Terminal Connections (terminal-connections) — Row 3 — Terminal Range1-12 and 47-50
Terminal Connections (terminal-connections) — Row 3 — SignalSIG
Terminal Connections (terminal-connections) — Row 3 — ConnectionInput 1 to 4
Terminal Connections (terminal-connections) — Row 4 — Terminal Range1-12 and 47-50
Terminal Connections (terminal-connections) — Row 4 — SignalIND *
Terminal Connections (terminal-connections) — Row 4 — ConnectionInput 1 to 4
Terminal Connections (terminal-connections) — Row 5 — Terminal Range13-16
Terminal Connections (terminal-connections) — Row 5 — Signal+
Terminal Connections (terminal-connections) — Row 5 — ConnectionExternal 24VDC input (18-36VDC). Optional.
Terminal Connections (terminal-connections) — Row 6 — Terminal Range13-16
Terminal Connections (terminal-connections) — Row 6 — Signal-
Terminal Connections (terminal-connections) — Row 6 — ConnectionExternal 24VDC input (18-36VDC). Optional.
Terminal Connections (terminal-connections) — Row 7 — Terminal Range17
Terminal Connections (terminal-connections) — Row 7 — SignalA+
Terminal Connections (terminal-connections) — Row 7 — ConnectionLoop IN & Loop OUT
Terminal Connections (terminal-connections) — Row 8 — Terminal Range18
Terminal Connections (terminal-connections) — Row 8 — SignalA-
Terminal Connections (terminal-connections) — Row 8 — ConnectionLoop IN & Loop OUT
Terminal Connections (terminal-connections) — Row 9 — Terminal Range21-22
Terminal Connections (terminal-connections) — Row 9 — Signal+
Terminal Connections (terminal-connections) — Row 9 — ConnectionIsolated 24VDC output (for local indications). Max 5 mA for local indicators. Note: Only active when external 24VDC input is connected to 13-16.
Terminal Connections (terminal-connections) — Row 10 — Terminal Range21-22
Terminal Connections (terminal-connections) — Row 10 — Signal-
Terminal Connections (terminal-connections) — Row 10 — ConnectionIsolated 24VDC output (for local indications). Max 5 mA for local indicators. Note: Only active when external 24VDC input is connected to 13-16.
Terminal Connections (terminal-connections) — Row 11 — Terminal Range23-46
Terminal Connections (terminal-connections) — Row 11 — SignalC
Terminal Connections (terminal-connections) — Row 11 — ConnectionOutput 1 to 4
Terminal Connections (terminal-connections) — Row 12 — Terminal Range23-46
Terminal Connections (terminal-connections) — Row 12 — SignalNC
Terminal Connections (terminal-connections) — Row 12 — ConnectionOutput 1 to 4
Terminal Connections (terminal-connections) — Row 13 — Terminal Range23-46
Terminal Connections (terminal-connections) — Row 13 — SignalNO
Terminal Connections (terminal-connections) — Row 13 — ConnectionOutput 1 to 4
System AssociationTS1000

Compatibility

    Manufacturer-listed system references

    System association
    TS1000

    Check the original document for configuration, installation conditions and restrictions.

    Original manufacturer documents and sources