Salwico IC21 WP Indication Control Unit
- Original manufacturer
- Consilium / Salwico
- Name
- Salwico IC21 WP Indication Control Unit
- Model
- Salwico IC21 WP
- Part number
- 5200270-00A
Supply availability and delivery time require confirmation. A catalog reference does not imply stock.
Specifications
| Manufacturer approvals / certifications | Not provided by manufacturer |
|---|---|
| Manufacturer Article Number | 5200270-00A |
| System | CS3000, CS4000, CS3004, Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish |
| Material | PC/ABS |
| Colour | Transparent/RAL7035 |
| Weight | approximately 530 g |
| External Nominal Voltage | 24 VDC |
| External Working Voltage | 19–30 VDC |
| External Max Current | 100 mA |
| Input Load Limit | 15 mA per input, pulsed |
| Pulse Length | 100 ms |
| Inputs | 2 inputs for closing contacts and/or proximity switches (NPN/PNP), 2- or 3-wire; local indication available |
| Outputs | Control of single and double doors |
| Loop Nominal Voltage | 35 VDC |
| Loop Working Voltage | 22–38 VDC |
| Loop Working Current | 0.3 mA |
| Input End Of Line | 30 kΩ (included) resistor |
| Ingress Protection | IP66 |
| Relative Humidity | 95% at low temperature; 93% ± 3% at high temperature |
| Ambient Temperature | -40 °C to +70 °C |
| Cable Gland | TET M20 for cable Ø8-13 mm |
| Cable Terminals | 2.5 mm² |
| Mandatory External Supply | External 24 VDC supply is mandatory. |
| Required Switch Settings | SW2 DIP 8 must always be ON; DIP 6 and DIP 7 are unused. SW901/SW902 detector range is required only for CM-21 replacement. |
| Door Supervision And Diodes | Without door supervision, jumper INP 2 terminals 4-5; EOL resistor is then unnecessary. Fit each door magnet with its own freewheeling diode and correct polarity. |
| Double-door Sequencing | When OUTPUT 3 is used for a double door, connect the first-door roller/limit switch to INPUT 5; MAG 2 releases only after the first door has closed and the switch opens. |
| Fire-door Fail-safe Scope | For CM-21 replacement, lost system communication closes fire doors after the SW2-selected watchdog timeout; follow the original detector-range and cause/effect setup. |
| Replacement Restrictions | Replacement dimensions differ; discard casing only where marked. Entries marked no replacement require contact with Consilium. |
Compatibility
- Requires technical confirmation; manufacturer compatibility evidence is not provided.
Accessories
- Not provided by manufacturer
Original documents & sources
Source pages
- https://www.consiliumsafety.com/content/uploads/products/en/5200270-00/5200270-00A_Salwico%20IC21%20WP_M_EN_2019_G.pdf
- https://www.consiliumsafety.com/en/product/ic21-wp-indication-ctrl-unit-5200270-00/
- https://www.consiliumsafety.com/content/uploads/2026/03/5200270-00_IC21-WP-INDICATION-CTRL-UNIT.png
Original manufacturer data retained. Product enquiry and technical sourcing by MAXONE Marine. Last reviewed: Not provided.