Connecting Global Safety Technology

Salwico IC21 WP Indication Control Unit

Original manufacturer
Consilium / Salwico
Name
Salwico IC21 WP Indication Control Unit
Model
Salwico IC21 WP
Part number
5200270-00A

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsNot provided by manufacturer
Manufacturer Article Number5200270-00A
SystemCS3000, CS4000, CS3004, Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
MaterialPC/ABS
ColourTransparent/RAL7035
Weightapproximately 530 g
External Nominal Voltage24 VDC
External Working Voltage19–30 VDC
External Max Current100 mA
Input Load Limit15 mA per input, pulsed
Pulse Length100 ms
Inputs2 inputs for closing contacts and/or proximity switches (NPN/PNP), 2- or 3-wire; local indication available
OutputsControl of single and double doors
Loop Nominal Voltage35 VDC
Loop Working Voltage22–38 VDC
Loop Working Current0.3 mA
Input End Of Line30 kΩ (included) resistor
Ingress ProtectionIP66
Relative Humidity95% at low temperature; 93% ± 3% at high temperature
Ambient Temperature-40 °C to +70 °C
Cable GlandTET M20 for cable Ø8-13 mm
Cable Terminals2.5 mm²
Mandatory External SupplyExternal 24 VDC supply is mandatory.
Required Switch SettingsSW2 DIP 8 must always be ON; DIP 6 and DIP 7 are unused. SW901/SW902 detector range is required only for CM-21 replacement.
Door Supervision And DiodesWithout door supervision, jumper INP 2 terminals 4-5; EOL resistor is then unnecessary. Fit each door magnet with its own freewheeling diode and correct polarity.
Double-door SequencingWhen OUTPUT 3 is used for a double door, connect the first-door roller/limit switch to INPUT 5; MAG 2 releases only after the first door has closed and the switch opens.
Fire-door Fail-safe ScopeFor CM-21 replacement, lost system communication closes fire doors after the SW2-selected watchdog timeout; follow the original detector-range and cause/effect setup.
Replacement RestrictionsReplacement dimensions differ; discard casing only where marked. Entries marked no replacement require contact with Consilium.

Compatibility

  • Requires technical confirmation; manufacturer compatibility evidence is not provided.

Accessories

  • Not provided by manufacturer

Original documents & sources