Connecting Global Safety Technology

Salwico IC21 WPL Indication Control Unit

Original manufacturer
Consilium / Salwico
Name
Salwico IC21 WPL Indication Control Unit
Model
Salwico IC21 WPL
Part number
5200278-00A

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsNot provided by manufacturer
Manufacturer Article Number5200278-00A
Inputs2 inputs for closing contacts and/or proximity switches (NPN/PNP), 2- or 3-wire. Local indication available.
OutputsControl of single and double doors.
Loop Nominal Voltage35 VDC
Loop Working Voltage22 - 38 VDC
Loop Working Current0.3 mA
Input End Of Line Resistor30kΩ (Included)
Ingress ProtectionIP66
Relative HumidityAt low temperature 95% At high temperature 93% ± 3%
Ambient Temperature-40°C to +70°C
Cable GlandTET M20 for cable Ø8-13mm
Mandatory External SupplyExternal 24 VDC supply is mandatory.
Required Switch SettingsSW2 DIP 8 must always be ON; DIP 6 and DIP 7 are unused. SW901/SW902 detector range is required only for CM-21 replacement.
Door Supervision And DiodesWithout door supervision, jumper INP 2 terminals 4-5; EOL resistor is then unnecessary. Fit each door magnet with its own freewheeling diode and correct polarity.
Double-door SequencingWhen OUTPUT 3 is used for a double door, connect the first-door roller/limit switch to INPUT 5; MAG 2 releases only after the first door has closed and the switch opens.
Fire-door Fail-safe ScopeFor CM-21 replacement, lost system communication closes fire doors after the SW2-selected watchdog timeout; follow the original detector-range and cause/effect setup.
Replacement RestrictionsReplacement dimensions differ; discard casing only where marked. Entries marked no replacement require contact with Consilium.
Cable Terminals2.5 mm²
MaterialPC/ABS
ColourTransparent/RAL7035
Weight~760 g
System CompatibilityCS3000, CS3004, CS4000, Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish
External Nominal Voltage24 VDC
External Working Voltage19-30 VDC
External Max Current100 mA
External Input Load Limit15 mA per input, pulsed
External Input Pulse Length100 ms

Compatibility

  • Requires technical confirmation; manufacturer compatibility evidence is not provided.

Accessories

  • Not provided by manufacturer

Original documents & sources