CS-Safety M H Fire/Fault/Disablement Safety Relay Module

Original manufacturer
Consilium / Salwico
Name
CS-Safety M H Fire/Fault/Disablement Safety Relay Module
Model
CS-Safety M H
Part number
5210001-00A

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsNot provided by manufacturer
Operating Voltage Range19–30 VDC
Current Consumption70 mA
Cable Terminals2.5 mm2
Operating Temperature-40 °C to +70 °C
Storage Temperature-50 °C to +70 °C
Relative Humidity≤ 95 % RH non-condensing
Addressing MethodDIP switch
Ethernet Port10/100 Mbit Auto Negotiation
Relay Output30 VDC, max 1 A resistive load
MaterialNylon 6.6
Weight (with Housing)≈140 g
ColourYellow (RAL 1018)
Spare Part (module)CS-Safety M 5210000-00A
Spare Part (housing)5210069-00A
Ce ConformityEN 54-2
Current Certificate ValidityNot provided by manufacturer
Safety Integrity LevelSIL 1 and SIL 2
Safety Architecture TypeType B
Hft0
Sff97 %
Pfd1.83 × 10-4
Pfd Calculation BasisMTTR 8 h and proof test interval 1 year
Xfire InputAn xFire signal input
Ssp BusAn SSP bus for communication with the CS-Loop M H and other CS-Safety M H modules
Redundant Power InputsTwo redundant 24 VDC power inputs
Safety Relay SignalsThree relay outputs reserved for signaling the fire, fault and disablement condition
Ethernet SspxtAn Ethernet interface for external protocols (SSPxt)
Address Dip Configuration8-pole DIP switch; binary value; poles 1 to 7 set the address
Safe Relay ConfigurabilityThe Safe Relays are not configurable.
Invalid Dip-switch ConditionAll LEDs flashing means all DIP switches are OFF or all are ON; set them according to project documentation.
MountingHorizontal 35 mm DIN rail
Source DatasheetData sheet no. 5210001-00A_CS-Safety M H_M_EN_2023_E
Specification Change NoticeThe specifications described herein are subject to change without notice.
Overall Width29.2 mm
Body Width22.6 mm
Height93.1 mm
Side Length107 mm
Protrusion4 mm
Internal CommunicationSSP Protocol; Backbone (BBI)
External CommunicationEthernet SSPxt
Production Mark2531/yy; yy = year of production
Cs-safety Terminal Numbers (terminal-numbers) — Row 1 — Source Column 2Ethernet
Cs-safety Terminal Numbers (terminal-numbers) — Row 1 — Source Column 3Ethernet interface
Cs-safety Terminal Numbers (terminal-numbers) — Row 2 — Source Column 121
Cs-safety Terminal Numbers (terminal-numbers) — Row 2 — Source Column 2NC
Cs-safety Terminal Numbers (terminal-numbers) — Row 2 — Source Column 3Common Fire Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 3 — Source Column 122
Cs-safety Terminal Numbers (terminal-numbers) — Row 3 — Source Column 2C
Cs-safety Terminal Numbers (terminal-numbers) — Row 3 — Source Column 3Common Fire Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 4 — Source Column 123
Cs-safety Terminal Numbers (terminal-numbers) — Row 4 — Source Column 2NO
Cs-safety Terminal Numbers (terminal-numbers) — Row 4 — Source Column 3Common Fire Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 5 — Source Column 124
Cs-safety Terminal Numbers (terminal-numbers) — Row 5 — Source Column 3Common Fire Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 6 — Source Column 131
Cs-safety Terminal Numbers (terminal-numbers) — Row 6 — Source Column 2NC
Cs-safety Terminal Numbers (terminal-numbers) — Row 6 — Source Column 3Common Fault Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 7 — Source Column 132
Cs-safety Terminal Numbers (terminal-numbers) — Row 7 — Source Column 2C
Cs-safety Terminal Numbers (terminal-numbers) — Row 7 — Source Column 3Common Fault Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 8 — Source Column 133
Cs-safety Terminal Numbers (terminal-numbers) — Row 8 — Source Column 2NO
Cs-safety Terminal Numbers (terminal-numbers) — Row 8 — Source Column 3Common Fault Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 9 — Source Column 134
Cs-safety Terminal Numbers (terminal-numbers) — Row 9 — Source Column 3Common Fault Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 10 — Source Column 141
Cs-safety Terminal Numbers (terminal-numbers) — Row 10 — Source Column 2SG
Cs-safety Terminal Numbers (terminal-numbers) — Row 10 — Source Column 3Not used
Cs-safety Terminal Numbers (terminal-numbers) — Row 11 — Source Column 142
Cs-safety Terminal Numbers (terminal-numbers) — Row 11 — Source Column 2D+
Cs-safety Terminal Numbers (terminal-numbers) — Row 11 — Source Column 3Not used
Cs-safety Terminal Numbers (terminal-numbers) — Row 12 — Source Column 143
Cs-safety Terminal Numbers (terminal-numbers) — Row 12 — Source Column 2D-
Cs-safety Terminal Numbers (terminal-numbers) — Row 12 — Source Column 3Not used
Cs-safety Terminal Numbers (terminal-numbers) — Row 13 — Source Column 144
Cs-safety Terminal Numbers (terminal-numbers) — Row 13 — Source Column 2NO
Cs-safety Terminal Numbers (terminal-numbers) — Row 13 — Source Column 3Common Disablement Relay output
Cs-safety Terminal Numbers (terminal-numbers) — Row 14 — Source Column 145
Cs-safety Terminal Numbers (terminal-numbers) — Row 14 — Source Column 2C
Cs-safety Terminal Numbers (terminal-numbers) — Row 14 — Source Column 3Common Disablement Relay output
Safe Relay Configurations (safe-relay-configurations) — Row 1 — OutputOutput
Safe Relay Configurations (safe-relay-configurations) — Row 1 — ConditionFire
Safe Relay Configurations (safe-relay-configurations) — Row 1 — Active LevelH
Safe Relay Configurations (safe-relay-configurations) — Row 1 — Cs-safety MX
Safe Relay Configurations (safe-relay-configurations) — Row 2 — OutputOutput
Safe Relay Configurations (safe-relay-configurations) — Row 2 — ConditionFault
Safe Relay Configurations (safe-relay-configurations) — Row 2 — Active LevelL
Safe Relay Configurations (safe-relay-configurations) — Row 2 — Cs-safety MX
Safe Relay Configurations (safe-relay-configurations) — Row 3 — OutputOutput
Safe Relay Configurations (safe-relay-configurations) — Row 3 — ConditionDisablement
Safe Relay Configurations (safe-relay-configurations) — Row 3 — Active LevelH
Safe Relay Configurations (safe-relay-configurations) — Row 3 — Cs-safety MX
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — IndicatorETH Lnk (Ethernet link connected)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — Colour / PatternGreen, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — Module StatusOK
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — IndicatorETH Lnk (Ethernet link connected)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — Colour / PatternNone
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — Module StatusNo communication
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — IndicatorETH Act (Ethernet activity)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — Colour / PatternGreen, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — Module StatusOK
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — IndicatorETH Act (Ethernet activity)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — Colour / PatternNone
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — Module StatusNo communication
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — IndicatorRS-485 Tx
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — Colour / PatternGreen, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — Module StatusOK
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — IndicatorRS-485 Tx
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — Colour / PatternNone
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — Module StatusNo communication
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — IndicatorRS-485 Rx
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — Colour / PatternGreen, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — Module StatusOK
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — IndicatorRS-485 Rx
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — Colour / PatternNone
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — Module StatusNo communication
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — IndicatorSSP (Communication)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — Colour / PatternGreen, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — Module StatusOK
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — IndicatorSSP (Communication)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — Colour / PatternNone
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — Module StatusNo communication
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — IndicatorFAULT
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — Colour / PatternYellow, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — Module StatusOne or more faults are present
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — IndicatorFAULT
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — Colour / PatternYellow, flashing
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — Module StatusModule is booting or re-scanning
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — IndicatorFAULT
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — Colour / PatternNone
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — Module StatusThere are no faults
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — IndicatorDIS (Disablement)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — Colour / PatternGreen, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — Module StatusOne or more disablements in the system
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — IndicatorFIRE
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — Colour / PatternRed, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — Module StatusOne or more alarms are present
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — Failure ClassificationFollow local procedures
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — IndicatorFIRE
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — Colour / PatternRed, flashing
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — Module StatusPre-alarm
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — Failure ClassificationFollow local procedures
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — IndicatorFIRE
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — Colour / PatternNone
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — Module StatusThere are no alarms
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — IndicatorPS (Power Supply)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — Colour / PatternGreen, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — Module StatusOK
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — Failure ClassificationN/A
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — IndicatorPS (Power Supply)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — Colour / PatternYellow, steady
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — Module StatusPower fault on one of the two power channels feeding the module. A single power fault does not prevent the safety module to communicate with the other modules.
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — Failure ClassificationMinor fault*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — IndicatorPS (Power Supply)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — Colour / PatternYellow, flashing: 0.5 sec On, 0.5 sec Off.
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — Module StatusBoot loader mode. Only active during firmware download to the module.
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — Failure Classification*
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — IndicatorPS (Power Supply)
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — Colour / PatternYellow, flashing: 1 sec On, 0.5 sec Off.
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — Module StatusSafe State Predefined state to avoid disturbing system integrity.
Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — Failure Classification*
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — IndicatorCOM (Backbone communication)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — Colour / PatternGreen, steady
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — Module StatusOK
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — Failure ClassificationN/A
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — IndicatorCOM (Backbone communication)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — Colour / PatternGreen, flashing
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — Module StatusUnconfigured. Could be a configuration error in the application program file. (Communication working)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — Failure ClassificationMinor fault*
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — IndicatorCOM (Backbone communication)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — Colour / PatternYellow, steady
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — Module StatusSystem fault.
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — Failure ClassificationMajor fault*
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — IndicatorCOM (Backbone communication)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — Colour / PatternYellow, steady
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — Module StatusCommunication fault on the backbone interface.
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — Failure ClassificationMajor fault*
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — IndicatorCOM (Backbone communication)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — Colour / PatternNone
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — Module StatusNo communication
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — Failure ClassificationMajor fault*
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — IndicatorPS + COM (both flashing)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — Colour / PatternPS Yellow, flashing
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — Module StatusTransferring software. (Download or upload.)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — Failure Classification*
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — IndicatorPS + COM (both flashing)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — Colour / PatternCOM Green, flashing
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — Module StatusTransferring software. (Download or upload.)
Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — Failure Classification*
System AssociationCFD5000

Compatibility

    Manufacturer-listed system references

    System association
    CFD5000

    Check the original document for configuration, installation conditions and restrictions.

    Original manufacturer documents and sources

    Accessories

    • Not provided by manufacturer

    Original documents & sources