CS-Safety M H Fire/Fault/Disablement Safety Relay Module
- Original manufacturer
- Consilium / Salwico
- Name
- CS-Safety M H Fire/Fault/Disablement Safety Relay Module
- Model
- CS-Safety M H
- Part number
- 5210001-00A
Supply availability and delivery time require confirmation. A catalog reference does not imply stock.
Specifications
| Manufacturer approvals / certifications | Not provided by manufacturer |
|---|---|
| Operating Voltage Range | 19–30 VDC |
| Current Consumption | 70 mA |
| Cable Terminals | 2.5 mm2 |
| Operating Temperature | -40 °C to +70 °C |
| Storage Temperature | -50 °C to +70 °C |
| Relative Humidity | ≤ 95 % RH non-condensing |
| Addressing Method | DIP switch |
| Ethernet Port | 10/100 Mbit Auto Negotiation |
| Relay Output | 30 VDC, max 1 A resistive load |
| Material | Nylon 6.6 |
| Weight (with Housing) | ≈140 g |
| Colour | Yellow (RAL 1018) |
| Spare Part (module) | CS-Safety M 5210000-00A |
| Spare Part (housing) | 5210069-00A |
| Ce Conformity | EN 54-2 |
| Current Certificate Validity | Not provided by manufacturer |
| Safety Integrity Level | SIL 1 and SIL 2 |
| Safety Architecture Type | Type B |
| Hft | 0 |
| Sff | 97 % |
| Pfd | 1.83 × 10-4 |
| Pfd Calculation Basis | MTTR 8 h and proof test interval 1 year |
| Xfire Input | An xFire signal input |
| Ssp Bus | An SSP bus for communication with the CS-Loop M H and other CS-Safety M H modules |
| Redundant Power Inputs | Two redundant 24 VDC power inputs |
| Safety Relay Signals | Three relay outputs reserved for signaling the fire, fault and disablement condition |
| Ethernet Sspxt | An Ethernet interface for external protocols (SSPxt) |
| Address Dip Configuration | 8-pole DIP switch; binary value; poles 1 to 7 set the address |
| Safe Relay Configurability | The Safe Relays are not configurable. |
| Invalid Dip-switch Condition | All LEDs flashing means all DIP switches are OFF or all are ON; set them according to project documentation. |
| Mounting | Horizontal 35 mm DIN rail |
| Source Datasheet | Data sheet no. 5210001-00A_CS-Safety M H_M_EN_2023_E |
| Specification Change Notice | The specifications described herein are subject to change without notice. |
| Overall Width | 29.2 mm |
| Body Width | 22.6 mm |
| Height | 93.1 mm |
| Side Length | 107 mm |
| Protrusion | 4 mm |
| Internal Communication | SSP Protocol; Backbone (BBI) |
| External Communication | Ethernet SSPxt |
| Production Mark | 2531/yy; yy = year of production |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 1 — Source Column 2 | Ethernet |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 1 — Source Column 3 | Ethernet interface |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 2 — Source Column 1 | 21 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 2 — Source Column 2 | NC |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 2 — Source Column 3 | Common Fire Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 3 — Source Column 1 | 22 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 3 — Source Column 2 | C |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 3 — Source Column 3 | Common Fire Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 4 — Source Column 1 | 23 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 4 — Source Column 2 | NO |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 4 — Source Column 3 | Common Fire Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 5 — Source Column 1 | 24 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 5 — Source Column 3 | Common Fire Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 6 — Source Column 1 | 31 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 6 — Source Column 2 | NC |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 6 — Source Column 3 | Common Fault Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 7 — Source Column 1 | 32 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 7 — Source Column 2 | C |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 7 — Source Column 3 | Common Fault Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 8 — Source Column 1 | 33 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 8 — Source Column 2 | NO |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 8 — Source Column 3 | Common Fault Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 9 — Source Column 1 | 34 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 9 — Source Column 3 | Common Fault Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 10 — Source Column 1 | 41 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 10 — Source Column 2 | SG |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 10 — Source Column 3 | Not used |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 11 — Source Column 1 | 42 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 11 — Source Column 2 | D+ |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 11 — Source Column 3 | Not used |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 12 — Source Column 1 | 43 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 12 — Source Column 2 | D- |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 12 — Source Column 3 | Not used |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 13 — Source Column 1 | 44 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 13 — Source Column 2 | NO |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 13 — Source Column 3 | Common Disablement Relay output |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 14 — Source Column 1 | 45 |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 14 — Source Column 2 | C |
| Cs-safety Terminal Numbers (terminal-numbers) — Row 14 — Source Column 3 | Common Disablement Relay output |
| Safe Relay Configurations (safe-relay-configurations) — Row 1 — Output | Output |
| Safe Relay Configurations (safe-relay-configurations) — Row 1 — Condition | Fire |
| Safe Relay Configurations (safe-relay-configurations) — Row 1 — Active Level | H |
| Safe Relay Configurations (safe-relay-configurations) — Row 1 — Cs-safety M | X |
| Safe Relay Configurations (safe-relay-configurations) — Row 2 — Output | Output |
| Safe Relay Configurations (safe-relay-configurations) — Row 2 — Condition | Fault |
| Safe Relay Configurations (safe-relay-configurations) — Row 2 — Active Level | L |
| Safe Relay Configurations (safe-relay-configurations) — Row 2 — Cs-safety M | X |
| Safe Relay Configurations (safe-relay-configurations) — Row 3 — Output | Output |
| Safe Relay Configurations (safe-relay-configurations) — Row 3 — Condition | Disablement |
| Safe Relay Configurations (safe-relay-configurations) — Row 3 — Active Level | H |
| Safe Relay Configurations (safe-relay-configurations) — Row 3 — Cs-safety M | X |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — Indicator | ETH Lnk (Ethernet link connected) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — Module Status | OK |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 1 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — Indicator | ETH Lnk (Ethernet link connected) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — Colour / Pattern | None |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — Module Status | No communication |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 2 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — Indicator | ETH Act (Ethernet activity) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — Module Status | OK |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 3 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — Indicator | ETH Act (Ethernet activity) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — Colour / Pattern | None |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — Module Status | No communication |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 4 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — Indicator | RS-485 Tx |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — Module Status | OK |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 5 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — Indicator | RS-485 Tx |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — Colour / Pattern | None |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — Module Status | No communication |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 6 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — Indicator | RS-485 Rx |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — Module Status | OK |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 7 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — Indicator | RS-485 Rx |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — Colour / Pattern | None |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — Module Status | No communication |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 8 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — Indicator | SSP (Communication) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — Module Status | OK |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 9 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — Indicator | SSP (Communication) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — Colour / Pattern | None |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — Module Status | No communication |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 10 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — Indicator | FAULT |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — Colour / Pattern | Yellow, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — Module Status | One or more faults are present |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 11 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — Indicator | FAULT |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — Colour / Pattern | Yellow, flashing |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — Module Status | Module is booting or re-scanning |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 12 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — Indicator | FAULT |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — Colour / Pattern | None |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — Module Status | There are no faults |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 13 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — Indicator | DIS (Disablement) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — Module Status | One or more disablements in the system |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 14 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — Indicator | FIRE |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — Colour / Pattern | Red, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — Module Status | One or more alarms are present |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 15 — Failure Classification | Follow local procedures |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — Indicator | FIRE |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — Colour / Pattern | Red, flashing |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — Module Status | Pre-alarm |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 16 — Failure Classification | Follow local procedures |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — Indicator | FIRE |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — Colour / Pattern | None |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — Module Status | There are no alarms |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 17 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — Indicator | PS (Power Supply) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — Module Status | OK |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 18 — Failure Classification | N/A |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — Indicator | PS (Power Supply) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — Colour / Pattern | Yellow, steady |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — Module Status | Power fault on one of the two power channels feeding the module. A single power fault does not prevent the safety module to communicate with the other modules. |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 19 — Failure Classification | Minor fault* |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — Indicator | PS (Power Supply) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — Colour / Pattern | Yellow, flashing: 0.5 sec On, 0.5 sec Off. |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — Module Status | Boot loader mode. Only active during firmware download to the module. |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 20 — Failure Classification | * |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — Indicator | PS (Power Supply) |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — Colour / Pattern | Yellow, flashing: 1 sec On, 0.5 sec Off. |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — Module Status | Safe State Predefined state to avoid disturbing system integrity. |
| Indicator And Safety States (page 3) (indicator-states-page-3) — Row 21 — Failure Classification | * |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — Indicator | COM (Backbone communication) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — Colour / Pattern | Green, steady |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — Module Status | OK |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 1 — Failure Classification | N/A |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — Indicator | COM (Backbone communication) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — Colour / Pattern | Green, flashing |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — Module Status | Unconfigured. Could be a configuration error in the application program file. (Communication working) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 2 — Failure Classification | Minor fault* |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — Indicator | COM (Backbone communication) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — Colour / Pattern | Yellow, steady |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — Module Status | System fault. |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 3 — Failure Classification | Major fault* |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — Indicator | COM (Backbone communication) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — Colour / Pattern | Yellow, steady |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — Module Status | Communication fault on the backbone interface. |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 4 — Failure Classification | Major fault* |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — Indicator | COM (Backbone communication) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — Colour / Pattern | None |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — Module Status | No communication |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 5 — Failure Classification | Major fault* |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — Indicator | PS + COM (both flashing) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — Colour / Pattern | PS Yellow, flashing |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — Module Status | Transferring software. (Download or upload.) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 6 — Failure Classification | * |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — Indicator | PS + COM (both flashing) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — Colour / Pattern | COM Green, flashing |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — Module Status | Transferring software. (Download or upload.) |
| Indicator And Safety States (page 4) (indicator-states-page-4) — Row 7 — Failure Classification | * |
| System Association | CFD5000 |
Compatibility
Manufacturer-listed system references
- System association
- CFD5000
Check the original document for configuration, installation conditions and restrictions.
Accessories
- Not provided by manufacturer
Original documents & sources
Source pages
Original manufacturer data retained. Product enquiry and technical sourcing by MAXONE Marine. Last reviewed: 2026-10-25T17:58:43.047396+00:00.