CS-PYH Programmable Smoke & Heat Detector
- Original manufacturer
- Consilium / Salwico
- Name
- CS-PYH Programmable Smoke & Heat Detector
- Model
- CS-PYH
- Part number
- 5210020-00A
Supply availability and delivery time require confirmation. A catalog reference does not imply stock.
Specifications
| Manufacturer approvals / certifications | UL268/521; EN50155; EN45545-2; SIL 1/2 environment suitability as printed. Current validity unknown. |
|---|---|
| Smoke Test / Replacement | When smoke-configured: Testifier/Solo 330; spray 1 s, wait 10 s, spray 1 s; repeat to red alarm. No alarm after 3 attempts: replace. Follow tester datasheet and system Service & Maintenance manual. |
| Ul Temperature Classes | Ordinary: operating 15–122 °F(-9 to+50 °C); installation 32–100 °F(0 to+38 °C). Intermediate: 15–167 °F(-9 to+75 °C); 32–150 °F(0 to+65 °C). |
| Detection Configurations | Heat-assisted smoke: TF2–TF5/TF8 for A1R/CS/CR; also heat-assisted smoke for A2S. Smoke: 5 sensitivity levels, default 3 Normal. |
| Contamination Compensation | Maintains sensitivity, avoids false alarms; slight contamination: warning/still operates; excess: fault alarm. Fine mesh limits chamber dust. |
| Humidity / Enclosure | 0–95% RH, non-condensing; polyamide6.6; white RAL9003; 110 g±5% without base. |
| Protective Cover | Keep through painting/dust work until area cleaned; remove all covers before system operation. |
| Ip Rating / Required Base | IP22 with UB-6-PA66 5100449-00A; IP44 with IP-BASE 5100774-00A. Rating depends on base. |
| Local Processing / Protocol | Local CPU alarm evaluation; IDAxt extends IDA for SIL 1/2 data integrity, reliability, robustness. |
| Functional-safety Data | Type B; HFT 0; SFF 95%; PFD avg 2.89×10^-4 at MTTR 8 h, proof-test interval 1 year. |
| En 54-5 Rate-of-rise Response | 10 °C/min: A1R from 25 °C in60–260 s; CR from 55 °C in120–330 s. A2S/CS: no alarm response. |
| Sub-loop / Safe I/o Limit | Current limited 5 mA; remote indication or supervised dry-contact reading. |
| Operating / Storage Temperature | Both -40 to+70 °C; UL ranges remain class-specific. |
| Compatible System / Sensing | CFD5000 T; addressable light-scatter smoke + thermistor heat sensing. |
| Sci Function | Isolates loop shorts; probe detects removal and restores without loop restart. |
| Manufacturer Part No. | 5210020-00A |
| Accessories / Connection | Bases: 5100449-00A/5100774-00A; adapter: 5100775-00A; CD-S 5100626(as printed). Wiring: IP-ADAPT/UB-6-PA66 datasheet; loop cable: system Installation & Commissioning manual. |
| Built-in Self-tests | Continuous hardware/A-D test; every 5 min, all internal/testable loop-unit communication paths from detection to fire reporting. Test log export: USB stick. |
| Test Equipment / Hazardous Areas | Testifier 5200112-00A; Solo 461 N1743(heat); Solo 330 N1738(smoke). Testifier/Solo 461 not approved in hazardous environments. |
| Printed Standards / Safety Scope | UL268/521; EN50155; EN45545-2; SIL 1/2 environment suitability as printed. Current validity unknown. |
| Sci Switching Thresholds | Open→Close 22±2 VDC; max non-energized-side load≈1.2 kΩ. Close→Open 14±2 VDC. |
| Original Dimensions | Ø104 mm; 50 mm overall height; 40.2 mm subordinate vertical dimension. Original four-page source retained. |
| Address Setting | 8-pole binary DIP: 1/2/4/8/16/32/64/128; addresses 1–150. Suitably sized pointed tool. |
| Safe I/o Configurations | Fault/General inputs: High/Low active, monitored for breaks/shorts. RIL output: active level NA, not monitored. |
| Cleaning Safety | Electrostatic charging hazard: exterior damp-cloth cleaning only to prevent static build-up. |
| Sci Current Limits | Ic max continuous 500 mA; Is max switching 800 mA; IL max short-circuit leakage <1 mA. |
| Operating Voltage / Current | 22–38 VDC; normal 0.1 mA±5%; alarm with LED activated 3 mA±5%. |
| Heat Test | When heat-configured: Testifier/Solo 461, apply heat until red alarm LED. |
| En 54-5 A1r / A2s | Application -40 to +50 °C. Response: A1R +54 to65 °C; A2S +54 to70 °C. |
| En 54-5 Cs / Cr | Application -40 to +80 °C; response +84 to100 °C for both classes. |
Compatibility
- CFD5000 T, as specified by the exact T_EN_2019_B source.
Accessories
- IP22 with UB-6-PA66 5100449-00A;IP44 with IP-BASE 5100774-00A.
- IP-ADAPT5100775-00A;CD-S5100626 as printed. Testifier5200112-00A,Solo461 N1743,Solo330 N1738;hazardous-environment restrictions apply.
Original documents & sources
Source pages
- https://www.consiliumsafety.com/content/uploads/products/en/5210020-00/5210020-00A_CS-PYH_T_EN_2019_B.pdf
- https://www.consiliumsafety.com/content/uploads/products/en/5210020-00/5210020-00A_CS-PYH_T_EN_2019_B.pdf
- https://www.consiliumsafety.com/content/uploads/products/en/5210020-00/5210020-00A_CS-PYH_T_EN_2019_B.pdf
Original manufacturer data retained. Product enquiry and technical sourcing by MAXONE Marine. Last reviewed: 2026-10-23T09:24:44.957219+00:00.