Connecting Global Safety Technology

C-GI ADDR Ex H Intrinsically Safe Loop Isolator

Original manufacturer
Consilium / Salwico
Name
C-GI ADDR Ex H Intrinsically Safe Loop Isolator
Model
C-GI ADDR Ex H
Part number
5600963-00

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsNot provided by manufacturer
Load-limit ApplicabilityFull limits apply if the external circuit has no combined lumped Li and Ci above 1% of the listed limits; OR L/C is distributed as cable; OR only lumped L or only lumped C is combined with cable.
Printed Ex Marking / AmbientII (1) G;[Ex ia Ga] IIC;-40 °C ≤ Ta ≤ +60 °C. This marking range is separate from the Data operating range -25 °C to +60 °C; no Zone rating inferred.
Loop Supply / Working VoltageLoop-powered from fire alarm panel, no separate supply. 27–38 V DC; nominal 36 V DC. Voltages are DC unless specified otherwise.
Other Combined-lumped CircuitsIn other situations with combined lumped inductance/capacitance, up to 50% of each listed L and C value is allowed.
Loop / Is Output TerminalsLoop IN:11(+),12(-); Loop OUT:13(+),14(-); IS line output:41(+),42(-). Preserve the original safe-area/IS-side drawing.
Printed Certificate ReferencesIMQ 19 ATEX 051; IECEx IMQ 19.0011; IEC 60079-0 and IEC 60079-11. Source references, not a claim of current validity.
Is Communication CapacitanceTo avoid communication-signal loss, capacitance on the intrinsically safe side must not exceed 300 nF.
Max Is Output Voltage Uo28 V
Max Is Output Power Po649.8 mW
Data Ambient Temperature-25 °C to +60 °C
Internal Ci / LiMaximum Ci 5.14 nF; Li negligible.
Ambient Humidity≤95% RH, non-condensing
Weight100 g ±5%
M-edition Compatible SystemsCS3000; CS4000; NSAC-1; Salwico Cargo; Salwico Cruise; Salwico LNG; Salwico Offshore; Salwico Ro/Pax; Salwico Workboat; Salwico Yacht; Salwico Navy; OEM Extinguish
Installation LocationNon-hazardous (safe) area; interface to Salwico IS addressable detectors/manual call points and IS line units.
Group Iib Connected-load LimitsCapacitance 640 nF; inductance 17 mH OR L/R ratio 199 µH/Ω. The separate 300 nF communication condition still applies.
Is / Non-is Conductor SeparationMinimum 50 mm separation; conductors between cable entrance and terminals must be as short as possible and must not cross sides.
Original Module Dimensions99 mm overall height;111 mm side length;22.6 mm front width. Original subdimensions:93.1 mm vertical and107 mm horizontal.
Loop CapacityMaximum 5 isolators per addressable detector loop; up to 20 IS line units per isolator.
Manufacturer Article Number5600963-00
Max Is Output Current Io92.8 mA
Group Iic Connected-load LimitsCapacitance 77 nF; inductance 4.3 mH OR L/R ratio 55 µH/Ω.
Material / ColourPolyamide (PA); Black RAL 9005 / Grey RAL 7042.
Cable TerminalsMaximum 2.5 mm² conductor
Ingress ProtectionIP20

Compatibility

  • M-edition scope: CS3000, CS4000, NSAC-1, Salwico Cargo, Salwico Cruise, Salwico LNG, Salwico Offshore, Salwico Ro/Pax, Salwico Workboat, Salwico Yacht, Salwico Navy, OEM Extinguish. I0 systems remain separate.

Accessories

  • Use compatible Salwico IS addressable detectors/manual call points; comply with IS/non-IS conductor separation and source-specific load conditions.

Original documents & sources

Source pages