Connecting Global Safety Technology

Micropack FDS303 Multi Spectrum IR Flame Detector (5101030-40A)

Original manufacturer
MICROPACK / Consilium
Name
Micropack FDS303 Multi Spectrum IR Flame Detector (5101030-40A)
Model
FDS303
Part number
5101030-40A

Supply availability and delivery time require confirmation. A catalog reference does not imply stock.

Specifications

Manufacturer approvals / certificationsPrinted certificates: ATEX FM18 ATEX 0040X (II 2 G); IECEx FME18.0003X (Ex db IIC T4); EN 54 1725-CPR-E0007; FM 3260; SIL 2 capable IEC 61508. Current validity unknown.
Manufacturer Article Number5101030-40A
Order RowFDS303IR3FLAMEDETSSSB 1xM25
MaterialStainless steel
Material LegendSS = Stainless Steel; AL = Aluminum (copper free)
Bracket TypeStandard bracket
Bracket Thickness3 mm
Marine Bracket ConditionMB shall be used in applications requiring DNV GL type approval; current validity unknown
Cable Entries1 x M25
Cable Glands IncludedNo
Weight6 kg (13.2 lbs)
ModelFDS303
ManufacturerMICROPACK
Catalog / SupplierConsilium
Compatible SystemsAll Consilium fire alarm systems
Detection PrincipleMulti spectrum IR flame detector
Explosion ProtectionExplosion proof multi spectrum IR flame detector
Nominal Supply Voltage24 V DC
Operating Voltage Range18-32 V DC
Power Consumption3 W minimum (no heater); 15 W maximum at 32 V DC with heater
Relay OutputsAlarm and fault
Current Output0-20 mA, HART
Output Modes0-20 mA (source non-isolated) and relay (alarm and fault), available simultaneously
Hart FunctionConfiguration only
Response TimeApprox. 5 seconds (typical)
Operating Temperature Range-60 °C to +85 °C (-76 °F to +185 °F)
Storage Temperature Range-60 °C to +85 °C (-76 °F to +185 °F)
Ambient Humidity0 to 100% RH (non-condensing)
Ingress ProtectionNEMA type 4X / IP66
Horizontal Field Of View90°
Vertical Field Of View90°
Generic Data-sheet Entries2×M25 (must not replace variant order-row entries)
N-heptane SensitivityStandard sensitivity: 30 × 30 cm (12 × 12 in.) at 30 m (98 ft)
Gasoline Sensitivity30 × 30 cm (12 × 12 in.) at 30 m (98 ft)
Jp4 Sensitivity30 × 30 cm (12 × 12 in.) at 30 m (98 ft)
Methane Sensitivity60 cm (24 in.) plume at 30 m (98 ft)
Ethanol Sensitivity30 × 30 cm (12 × 12 in.) at 30 m (98 ft)
MountingCeiling or wall; vertical adjustment 0° to 45°; horizontal rotation ±45°
Wall Mounting RestrictionAllow space for cable gland and cable; otherwise downward rotation may be restricted
Wiring TerminalsRear enclosure section; remove end cap; view looking inside detector
0-20 Ma Fixed Values0 mA power/detector fault; 1.5 mA optical fault; 4 mA healthy; 18 mA alarm; 21 mA over-range
0-20 Ma Tolerance±0.3 mA DC; maximum loop resistance 500 ohm
Relay WiringRelay output wiring options; EOL and alarm resistor values defined by client and control system/fire panel
Rs485 ConfigurationThe source describes a configuration-only procedure: reversing terminals 1/2 enables Micropack RS485 on 3/4 with Micropack applications. Follow manual 3303.0001; this is not normal supply wiring.
Optical Self-testContinuous optical test without reflector; verifies operation and improves device up-time
Hazardous Area WarningSee FDS303 Safety & Technical Manual 3303.0001 for further information and hazardous-area installation
Installation WarningRefer to FDS303 technical manual 3303.0001 before installing or maintaining; do not open if explosive atmosphere may be present
Maintenance RestrictionFront section only accessed by trained personnel
Safety Manual Review StatusManual 3303.0001 is referenced by the datasheet and has not been reviewed for this catalog summary.
Atex Certificate And ClassificationFM18 ATEX 0040X; ATEX II 2 G; 60079-0, 60079-1.
Iecex Certificate And StandardIECEx FME18.0003X; Ex db IIC T4; 60079-0, 60079-1
Fm And Nec ApprovalsFM 3260; NEC 505 Class 1 Zone 1 AEx/Ex d IIC T4; NEC 500 Class 1 Division 1 Groups B,C,D T4
Printed Iecex Approval Ambient-60 °C to +85 °C (approval ambient; not the separately stated operating range)
Fm / Nec Approval Ambient-50 °C to +85 °C (FM/NEC ambient; not the separately stated operating range)
Sil CapabilitySIL 2 capable according to IEC 61508
En 54 Certificate And Standard1725-CPR-E0007; EN 54-10:2002+A1:2005
Declaration Of PerformanceDoP D of P FDS303 2018
Certification Validity StatusPrinted / historical; current validity unknown
Heated Optics ControlMicroprocessor controlled heated optics; maintains operation in harsh weather conditions (snow, ice, condensation)
External Flame Simulator TestExternal testing with a long-range flame simulator; minimises the need for scaffolding
Flame Simulator AccessoryCD-FS-30X flame simulator; 5100791-00A
Spare Marine Bracket AccessoryMarine bracket (spare only); 5101032-00A
Spare Standard Bracket AccessoryStandard bracket (spare only); 5101033-00A
Detector Sealing Kit AccessoryDetector sealing kit (gland seals and O ring set); 5101093-00A
Original Source Drawing RequirementReview the 9-page original for pages 4-6 connections, page 7 dimensions, and pages 8-9 standard/marine bracket drawings; do not transcribe unverified diagram values

Compatibility

  • All Consilium fire alarm systems

Accessories

  • CD-FS-30X flame simulator 5100791-00A
  • Marine bracket (spare only) 5101032-00A
  • Standard bracket (spare only) 5101033-00A
  • Detector sealing kit (gland seals and O ring set) 5101093-00A