Micropack FDS303 Multi Spectrum IR Flame Detector (5101031-00A)
- Original manufacturer
- MICROPACK / Consilium
- Name
- Micropack FDS303 Multi Spectrum IR Flame Detector (5101031-00A)
- Model
- FDS303
- Part number
- 5101031-00A
Supply availability and delivery time require confirmation. A catalog reference does not imply stock.
Specifications
| Manufacturer approvals / certifications | Printed certificates: ATEX FM18 ATEX 0040X (II 2 G); IECEx FME18.0003X (Ex db IIC T4); EN 54 1725-CPR-E0007; FM 3260; SIL 2 capable IEC 61508. Current validity unknown. |
|---|---|
| Manufacturer Article Number | 5101031-00A |
| Order Row | FDS303IR3FLAMEDETALSB 2xM25 |
| Material | Aluminium (copper free) |
| Material Legend | SS = Stainless Steel; AL = Aluminum (copper free) |
| Bracket Type | Standard bracket |
| Bracket Thickness | 3 mm |
| Marine Bracket Condition | MB shall be used in applications requiring DNV GL type approval; current validity unknown |
| Cable Entries | 2 x M25 |
| Cable Glands Included | No |
| Weight | 2.5 kg (5.5 lbs) |
| Model | FDS303 |
| Manufacturer | MICROPACK |
| Catalog / Supplier | Consilium |
| Compatible Systems | All Consilium fire alarm systems |
| Detection Principle | Multi spectrum IR flame detector |
| Explosion Protection | Explosion proof multi spectrum IR flame detector |
| Nominal Supply Voltage | 24 V DC |
| Operating Voltage Range | 18-32 V DC |
| Power Consumption | 3 W minimum (no heater); 15 W maximum at 32 V DC with heater |
| Relay Outputs | Alarm and fault |
| Current Output | 0-20 mA, HART |
| Output Modes | 0-20 mA (source non-isolated) and relay (alarm and fault), available simultaneously |
| Hart Function | Configuration only |
| Response Time | Approx. 5 seconds (typical) |
| Operating Temperature Range | -60 °C to +85 °C (-76 °F to +185 °F) |
| Storage Temperature Range | -60 °C to +85 °C (-76 °F to +185 °F) |
| Ambient Humidity | 0 to 100% RH (non-condensing) |
| Ingress Protection | NEMA type 4X / IP66 |
| Horizontal Field Of View | 90° |
| Vertical Field Of View | 90° |
| Generic Data-sheet Entries | 2×M25 (must not replace variant order-row entries) |
| N-heptane Sensitivity | Standard sensitivity: 30 × 30 cm (12 × 12 in.) at 30 m (98 ft) |
| Gasoline Sensitivity | 30 × 30 cm (12 × 12 in.) at 30 m (98 ft) |
| Jp4 Sensitivity | 30 × 30 cm (12 × 12 in.) at 30 m (98 ft) |
| Methane Sensitivity | 60 cm (24 in.) plume at 30 m (98 ft) |
| Ethanol Sensitivity | 30 × 30 cm (12 × 12 in.) at 30 m (98 ft) |
| Mounting | Ceiling or wall; vertical adjustment 0° to 45°; horizontal rotation ±45° |
| Wall Mounting Restriction | Allow space for cable gland and cable; otherwise downward rotation may be restricted |
| Wiring Terminals | Rear enclosure section; remove end cap; view looking inside detector |
| 0-20 Ma Fixed Values | 0 mA power/detector fault; 1.5 mA optical fault; 4 mA healthy; 18 mA alarm; 21 mA over-range |
| 0-20 Ma Tolerance | ±0.3 mA DC; maximum loop resistance 500 ohm |
| Relay Wiring | Relay output wiring options; EOL and alarm resistor values defined by client and control system/fire panel |
| Rs485 Configuration | The source describes a configuration-only procedure: reversing terminals 1/2 enables Micropack RS485 on 3/4 with Micropack applications. Follow manual 3303.0001; this is not normal supply wiring. |
| Optical Self-test | Continuous optical test without reflector; verifies operation and improves device up-time |
| Hazardous Area Warning | See FDS303 Safety & Technical Manual 3303.0001 for further information and hazardous-area installation |
| Installation Warning | Refer to FDS303 technical manual 3303.0001 before installing or maintaining; do not open if explosive atmosphere may be present |
| Maintenance Restriction | Front section only accessed by trained personnel |
| Safety Manual Review Status | Manual 3303.0001 is referenced by the datasheet and has not been reviewed for this catalog summary. |
| Atex Certificate And Classification | FM18 ATEX 0040X; ATEX II 2 G; 60079-0, 60079-1. |
| Iecex Certificate And Standard | IECEx FME18.0003X; Ex db IIC T4; 60079-0, 60079-1 |
| Fm And Nec Approvals | FM 3260; NEC 505 Class 1 Zone 1 AEx/Ex d IIC T4; NEC 500 Class 1 Division 1 Groups B,C,D T4 |
| Printed Iecex Approval Ambient | -60 °C to +85 °C (approval ambient; not the separately stated operating range) |
| Fm / Nec Approval Ambient | -50 °C to +85 °C (FM/NEC ambient; not the separately stated operating range) |
| Sil Capability | SIL 2 capable according to IEC 61508 |
| En 54 Certificate And Standard | 1725-CPR-E0007; EN 54-10:2002+A1:2005 |
| Declaration Of Performance | DoP D of P FDS303 2018 |
| Certification Validity Status | Printed / historical; current validity unknown |
| Heated Optics Control | Microprocessor controlled heated optics; maintains operation in harsh weather conditions (snow, ice, condensation) |
| External Flame Simulator Test | External testing with a long-range flame simulator; minimises the need for scaffolding |
| Flame Simulator Accessory | CD-FS-30X flame simulator; 5100791-00A |
| Spare Marine Bracket Accessory | Marine bracket (spare only); 5101032-00A |
| Spare Standard Bracket Accessory | Standard bracket (spare only); 5101033-00A |
| Detector Sealing Kit Accessory | Detector sealing kit (gland seals and O ring set); 5101093-00A |
| Original Source Drawing Requirement | Review the 9-page original for pages 4-6 connections, page 7 dimensions, and pages 8-9 standard/marine bracket drawings; do not transcribe unverified diagram values |
Compatibility
- All Consilium fire alarm systems
Accessories
- CD-FS-30X flame simulator 5100791-00A
- Marine bracket (spare only) 5101032-00A
- Standard bracket (spare only) 5101033-00A
- Detector sealing kit (gland seals and O ring set) 5101093-00A
Original documents & sources
Source pages
- https://www.consiliumsafety.com/content/uploads/products/en/5101030-00/5101030%2C%205101031%2C%205101225_FDS303_I0_EN_2022_C.pdf
- https://www.consiliumsafety.com/content/uploads/products/en/5101030-00/5101030%2C%205101031%2C%205101225_FDS303_I0_EN_2022_C.pdf
- https://www.consiliumsafety.com/content/uploads/products/en/5101030-00/5101030%2C%205101031%2C%205101225_FDS303_I0_EN_2022_C.pdf
Original manufacturer data retained. Product enquiry and technical sourcing by MAXONE Marine. Last reviewed: 2026-10-23T12:21:56.908746+00:00.